RESIDUAL CURRENT RELAY
WITH A SEPARATED TOROIDAL TRANSFORMER
TYPE B (MRCD – Modular Residual Current device)

By11600

By11600 is a differential electrical protection to be installed where required. It intervenes in case of failure.
By11600 allows to establish, according to the various possible settings, intervention selectivity criteria in complex industrial plants

  • Three DIN modules
  • Graphic display (Ink look)
  • RMS measures
  • Alarm (trip) relay: changeover contact
  • Pre-alarm relay: changeover contact
  • Relays that can be set for "Positive Safety" behavior
  • Remote reset (Vac - Vdc)
  • Single TORB toroid with through hole Ømm 35 - 60 - 80 - 110 - 160 - 210
  • Tripping times separately selectable for (Tripping) Alarm or Pre-alarm
  • Tripping thresholds separately selectable for (Tripping) Alarm or Pre-alarm
  • Current sensor diagnostics TORB toroid "Disconnected" or "Short circuit"
  • New version with extended maximum operating current (Tab1. pag. 3.3 User Manual)

Settings

IΔn (fault current):

30, 100, 200, 300, 500 mA
1, 3 A, 5 A, 10 A

 
 

Time:

(30 mA = Ist) 100, 200, 300, 400, 500, 750 msec, 1, 5, 10 sec

 

Reference Standards

  • CEI EN 60947-2 :2019-03 “Annex M” MRCD type B
    (identical to EN 60947-2:2017-10 and IEC 60947-2:2016-06/COR1:2016 Ann. M)
  • CEI EN 61869-2 :2014-05
    (identical to EN 61869-2:2012-11 and IEC 61869-2:2012-09)
  • European Directive LVD 2014/35/EU
  • Electromagnetic Compatibility: (EN edition in force in November 2019)
    EN 61000-4-2
    EN 61000-4-5
    EN 55016-2-3
    EN 61000-4-3
    EN 61000-4-6
    EN 61000-3-2
    EN 61000-4-4
    EN 55016-2-1
    EN 61000-3-3

NOTE

MRCM (Modular Residual Current Monitor) devices cannot replace MRCD devices in the function of safety device in case of failure.

 

AVAILABLE DOCUMENTATION

Brochure
Download
Datasheet
Download
User Manual (FW: 02.01.00)
Download
User Manual (FW: 02.01.01)
Download
User Manual (FW: 02.01.02)
Download

 

Application fields

  • Equipments containing frequency converters (inverters)
    Lifts, machine tools, robotics, manipulators, transfer lines, fans, circulation pumps, centrifugal pumps, conveyor belts, agitators, mixers, dryers, dosing machines, packaging machines, mills, centrifuges, machines for the wood industry, textile machines ...
  • Equipment containing AC to DC converters (with three-phase bridges, thyristors, Gate Turn Off ...)
    Extruders for plastic materials, paper mills, lifting systems, iron and steel industry, presses, dies ...
  • Equipment containing DC to AC converters (PV)
    Photovoltaic systems, industrial DC power supplies for electroplating ...
  • Charging stations for vehicles

 

TOROIDS (TORB)

The current sensors combined with the By11600 are the toroidal current reducers series TORB (see here) and TORB HV (see here).